Download PDF version

In May 2021, sparks in a ventilator ignited a deadly blaze in the intensive care unit of a COVID-19 treatment building at an Indian hospital. Investigations into the incident later revealed a variety of gaps in the building’s fire protection measures.

While incidents of this severity are thankfully relatively rare, this tragic example serves to remind us of the particular risks associated with healthcare settings. The presence of countless fire hazards, the difficulties of effectively maintaining fire protection across large and complex sites, combined with a high density of people – many of whom are very vulnerable – all serve to underline how easily a fire can bring essential services to a standstill, put lives at risk, and at worst lead to needless loss of life.

The standard of fire safety in healthcare facilities is directly related to the quality and effective implementation of the fire risk assessment as well as the adequate provision of physical fire protection. At the core of many of these physical fire protection measures is the fire alarm control panel, with the most sophisticated of these capable of addressing the day-to-day challenges encountered by hospitals, clinics, care homes, and their staff.

Immediate and Uninterrupted Notification of Alarm

Networked fire systems can be relied upon to control evacuation procedures from a central or various locations Hospitals are complex, often combining old and new buildings and spanning tens of thousands of square meters, with numerous departments such as A&E, critical care, specialist treatment centers, operating theatres, and wards. In these settings, networked fire systems deliver the greatest benefits.

Networked fire systems can be relied upon to control evacuation procedures from a central location or various locations, and can be programmed to effectively reduce the number of false alarms. They work with third-party systems to control the release of suppressants, operate smoke control systems, manage the closure and release of fire doors, link to graphical control systems, and interact with building management systems (BMS).

To do all of this effectively, the fire panels installed on these sites must communicate instantaneously with one another across vast networks, with miles of cabling. These systems need to work quickly and reliably and process large numbers of changing signals in the event of a real fire situation. On larger healthcare sites, seconds count and fast systems are highly valuable in maximizing the time for verification, escape and firefighting.

MxPro 5 and Axis EN

The MxPro 5 and Axis EN ranges of fire alarm control panels from global fire systems manufacturer Advanced offer some of the industry’s most comprehensive and state-of-the-art networking capabilities.

Advanced networks can be configured to allow the inter-connection of up to 200 panels (nodes) in a fault-tolerant configuration, relaying fire alarm signals across a complete 200-panel system in just 3.5 seconds. Using EN54-13 approved panels gives peace of mind that the system is designed and tested to continuously monitor network activity and ensure each panel performs in a fire situation.

Practical Solutions for Sensitive Notification of Alarm

Nurse Workstations

In critical care areas such as intensive care units, patients are often immobile and likely to be connected to medical equipment. In a fire scenario, staff responsible for high-dependency patients need to be able to monitor the situation as it evolves, without causing panic and distress for those in their care. For this reason, sounders and speakers aren’t always required, and instead, fire system repeater panels can be used.

Advanced offers four types of remote terminals to complement its fire panels

Repeater panels, located in strategic locations such as nurse workstations, provide early notification of any fire detection events as well as system monitoring. Discreet and early notification affords staff time to prepare, and up-to-the-minute system status information enables them to make educated decisions on when it’s best to remain in place, shelter or evacuate.

Advanced offers four types of remote terminals to complement its fire panels, each providing varying levels of control and functionality depending on requirements.  TouchControl is a low-profile, high-resolution 10-inch touchscreen that lets users check the status of the fire system using interactive site maps and zone plans.

Ideal for use in public areas such as wards and hospital wings thanks to its low-profile design, the panel complements a wide range of interiors and has the added benefit of being able to display notices and presentations when in standby mode. The screen instantly reverts to fire operation as soon as it is touched, or a fire condition occurs.

Staff Paging and Deaf Alert

Advanced is witnessing increasing demand from healthcare premises for discreet methods of alerting staff to fire alarm communications, particularly when they are working in areas with vulnerable patients.

A radio-based messaging pager can be used to both subtly alert staff, without causing panic to patients, and to provide notification to the hard of hearing to the need to evacuate in emergency situations. This is particularly important for healthcare facilities that are required to meet legal obligations pertaining to disabilities. For example, in the UK, premises are required to ensure that they are Disability Discrimination Act (DDA) compliant.

LifeLine is Advanced’s three-in-one ESPA pager unit that delivers deaf and hearing-impaired alerts, detailed fire paging for engineers as well as instant staff paging. LifeLine provides clear and instant transmission of fire alarm alerts, information and emergency communications via personal pagers, it can be integrated into the fire system and is designed for compliance with BS 5839-1 section 18.

Flashing Beacons and Strobes

Flashing beacons or strobes provide another valuable way of discreetly notifying healthcare staff of a fire situation Flashing beacons or strobes provide another valuable way of discreetly notifying healthcare staff of a fire situation in cases where an audible alarm may cause issues. These visual warning devices are intended for use as part of the fire alarm system, but it is important to remember to choose those that have been independently certified to meet the requirements of the EN 54-23 product standard.

Although full consideration must be given to any patients and staff who may be photo-sensitive or adversely affected by flashing lights, beacons and strobes can deliver an effective warning of a fire emergency.

False Alarm Management

False and unwanted fire alarms are one of the biggest issues in fire safety and building management today. They do not only leave occupants confused and troubled but can also lead to complacency and a failure to take proper action if/when a real fire occurs. They are also increasingly subject to penalty charges from fire and rescue services across the globe.

A high-performance fire system should offer the flexibility to accommodate the various evacuation strategies required in healthcare settings. False Alarm Management (FAM) generally uses detection methods and human verification of alarms to help reduce the incidence of false alarms. For example, algorithms in detection heads can increasingly differentiate between false signals such as steam or burning toast and actual fires.

Panels can also allow detectors to work smarter, using double knock (operation of two detectors) or coincidence (both combined smoke and heat detection elements operating) to confirm a fire. The system can respond differently to heat and smoke (with multi-sensors) and for programmable detector sensitivities.

Alarm verification times and investigation delays can be programmed to operate at different times of day, allowing strategies to be configured relevant to the level of staff on duty or if the usage of an area changes. Systems can also include dedicated input devices that are manually operated when a false alarm is suspected to allow trained staff to extend an investigation period so that a local alarm signal can be verified before escalating.

Advanced has published AlarmCalm – Complete False Alarm Management highlighting solutions for care homes

To highlight some of the solutions to the challenges faced in care homes, Advanced has published AlarmCalm – Complete False Alarm Management for care homes. The document outlines the features of Advanced’s AlarmCalm false alarm management solution and its key components, as well as providing an overview of the areas within care homes where different false alarm strategies may be required, based on risk, building design, and resident needs.

Integration with Third-Party Systems

A high-performance fire system, capable of interfacing with third-party BMS, smoke damper control, sprinkler monitoring, or HVAC systems, offers the user a host of advantages. By consolidating data from HVAC, energy, security, CCTV, and life safety applications onto one system, the user gains facility-wide insight from a single workstation – benefiting from improved reporting, information management, and decision making.

Against a backdrop of increasing pressures to drive down costs amongst healthcare operators without compromising protection, operational efficiencies can be gained through the integration of the fire system and BMS, thanks to the reduced requirement for additional staffing, simplified training, and fewer false alarms.

BMS Interface

Advanced’s BMS interface allows any MxPro 5 or Axis EN system to interconnect and communicate with independent third-party building management systems, as well as PC-based graphical control systems. This allows the fire system to be managed using existing fire or facilities management systems.

In larger sites, such as hospitals, multiple BMS interfaces can be connected to an AdNet network allowing independent connections to a wide range of control systems.

keeping healthcare premises compliant

The fire protection requirements for healthcare premises are wide-ranging. They require meticulous planning and customization to accommodate an array of building uses, staff, and patient needs. Ensuring that the systems installed are completely reliable and fully functioning at all times has to be given the highest priority in these critical settings.

Advanced continues to gather feedback from its many healthcare customers and innovates accordingly to help simplify the complex task of keeping healthcare premises compliant and their occupants safe from fire.

Download PDF version Download PDF version

In case you missed it

How Does Thermal Imaging Serve The Needs Of Firefighters?
How Does Thermal Imaging Serve The Needs Of Firefighters?

Thermal imaging is an advantageous tool for firefighters on the frontline. As thermal cameras have become more compact and affordable, their availability has expanded, along with their usefulness. We asked our Expert Panel Roundtable: How does thermal imaging serve the needs of firefighters and how is it changing?  

Why Should I Consider Fire Water Runoff?
Why Should I Consider Fire Water Runoff?

Fires have devastating consequences, not just posing a threat to property, but also to human life. Fires can also have detrimental impacts on the environment, with one of the largest associated environmental issues being water runoff occurring from tackling the fire. What is Fire Water Runoff? - Water is widely used to extinguish fire, thanks to its accessibility and effectiveness. Typically, water isn’t hazardous and doesn’t pose any threats, however, it can easily become contaminated by any materials stored onsite, or combustion by-products. Some water will evaporate with the fire, some will infiltrate into the ground, and any excess will runoff. Managing fire water runoff What are the Risks? - Fire water runoff can contain chemicals which are toxic to soils, drinking water, and aquatic life in surface water. Runoff can enter the environment through various pathways, including absorption into the ground, draining into both surface and foul drains, or runoff into bodies of water. The resulting pollution can cause detrimental environmental harm particularly if groundwater becomes contaminated, and even pose a threat to public health. Fire water can carry contaminants a long distance, expanding the impacted area Fire water can carry contaminants a long distance, expanding the impacted area. Alongside the environmental impacts, the ‘polluter pays’ principle underpins most of the regulation of pollution affecting land, water and air quality. If you do not manage fire water runoff, you could be prosecuted and be liable for the clean-up costs. Flood risk assessment How to Identify Risk? - It is important to carry out a thorough risk assessment. If you are yet to move into a property a thorough flood risk assessment is recommended, however, all businesses should consider their fire water regardless of how long they have been at a site. Enlisting a specialist will make the process much easier, and ensure it is carried out accurately, efficiently, and in-line with best practice and guidance. It’s important this step is undertaken before there could be any potential risk from fire to ensure a thorough plan and procedure is in place. The risk assessment should consider areas such as the site topography, drainage connectivity, materials and substances stored on site, along with the current storage arrangements. There should also be consideration given to how much water is likely to be required to extinguish a fire. Robust emergency plans Having the necessary policies and procedures in place will undoubtedly reduce the potential impact As part of the risk assessment, a drainage plan should be created and recorded, which will also be useful for site maintenance. Ideally, all relevant information should be stored within accessible BIM (Building Information Modeling) software. Having the necessary policies and procedures in place will undoubtedly reduce the potential impact. All businesses should have robust emergency plans, with higher risk businesses such as COMAH (Control of Major Accident Hazards) sites legally required to have more comprehensive and detailed plans. Many commercial and industrial sites store potentially hazardous chemicals or materials, which would be highly polluting should they enter a watercourse with fire water. The subsequent runoff can lead to a major accident to the environment. Preventing fire water To prevent fire water from causing pollution, it can be contained, reducing the risk of contamination occurring. There are various methods for containment which may include: Drainage shut off valves. Bunds. Containment lagoons or underground storage tanks. More simple methods can include aspects such as drainage covers or spill kits. An experienced and qualified professional will be able to help you prepare for managing your fire water. Environmental protection is of paramount importance, and by assessing and managing the associated risks, natural resources and ecosystems can be safeguarded. Notwithstanding a company’s regulatory obligations, and noting that in the vast majority of instances the ‘polluter pays’, the expectations of Corporate Social Responsibility alone make it good practice to demonstrate exemplary environmental compliance. Our team at FPS Environmental can help you by creating a fire water management plan which will identify ways to support water pollution prevention.

Teledyne’s Handheld Laser Detects Explosive Methane From 100 Feet Away
Teledyne’s Handheld Laser Detects Explosive Methane From 100 Feet Away

A new handheld device can detect the presence of explosive methane gas from up to 100 feet away. For firefighters, the tool provides situational awareness, saves time, and ensures safety from a distance. Knowing the presence of methane gas enables a firefighter to deal with an emergency gas leak and to avoid a deadly explosion. Gas laser The Gas Laser from Teledyne Gas and Flame Detection can shoot a laser beam through a window, a gap in a door, or another common venting point to provide an instant reading of the amount of methane in an area up to 100 feet away. The laser is invisible, but a green-spot pointer guides the aim as a user “points and shoots.” The laser bounces off any reflective object and then analyses the parts per million (ppm) of methane gas per meter of distance along the path of the laser. It measures down to a threshold of 1.25 ppm/meter. The handheld device can also capture a video image and a GPS location in addition to the gas reading stored on the device. It can be connected via WiFi and/or Bluetooth to a smartphone or other device and has onboard data logging. The device is automatically calibrated and tested when it is returned to its case. Detects minute quantities of methane Gas laser detects a much smaller amount of methane than would be explosive, thus preventing explosions  “It’s a brand new device, and everybody wants it,” says Alan Skinner, Regional Manager, Portable Gas Detection for Teledyne Gas and Flame Detection. “Once they understand what it does, they want it. Now you don’t have to be inside a hazard to detect the hazard.” The Gas Laser detects a much smaller amount of methane than would be explosive, thus preventing explosions by addressing leaks early.  The lower explosive limit (LEL) for methane is 5 percent, the equivalent of 50,000 ppm, much higher than the measurement threshold of the Gas Laser. Previously, there was no entirely safe method of evaluating the gas concentration without being near an area, typically using a three-foot probe sensor, for example.  “Now they know what they are getting into before they enter,” says Skinner. “It saves a huge amount of time.” Understanding working of gas laser Getting the word out about the device has been a challenge given the continuing coronavirus pandemic and disruptions of the hurricane season. “It’s one of those products you have to show them and let them play with it to understand what it does,” says Skinner. Interest was high at the recent FDIC show, where Teledyne unveiled the new sensor alongside its broader range of gas detection sensors. Teledyne’s range of portable sensors traces its roots back to GM Instruments (GMI), founded in Scotland in 1947. The sensor company was involved in multiple mergers and acquisitions in recent years, including ownership by companies such as Battery Ventures, Tyco, Scott Instruments, Johnson Controls, and 3M. Two years ago, the product line was acquired by Teledyne and represents the portables segment of their Environmental Monitoring Division, which also includes Detcon, Simtronics, and Oldham. Protege ZM and PS200 sensor PS200 sensor measures levels of four gases – methane, oxygen, carbon monoxide, and hydrogen sulfide Another sensor among Teledyne’s range of handheld devices is the Protégé ZM, a carbon monoxide sensor that a fireman can clip to their helmet, pocket, or bag. The “disposable” device has a 24-month lifespan, requires zero maintenance, and provides a calibration and bump test. The PS200 sensor measures levels of four gases – methane, oxygen, carbon monoxide, and hydrogen sulfide. An internal pump extracts a sample before a firefighter enters a confined space. A charge, bump, and calibration station (ABC Station) ensures calibration on a weekly, monthly, or twice-yearly basis. PS500 and GT Fire sensor The PS500 model adds another sensor to the four – typically either a photoionization detector (PID) for volatile organic compounds such as benzene, or a hydrogen cyanide (HCN) sensor to measure the presence of carcinogenic compounds that can be a byproduct of burning vinyl or plastics. The PID sensor can help investigators detect propellants that might indicate arson. The GT Fire sensor detects explosive gases in the PPM/LEL ranges with optional CO, H2S, and O2 sensors. The device can sniff out small gas leaks before any LEL level is reached. Able to find leaks in the PPM range, the device can pinpoint exactly where gas is leaking.

vfd