Dr Steve Harrison, Product Engineering Manager at ASL Safety & Security, considers certification requirements in the voice alarm (VA) sector and how pending new standards will differ from predecessors. What's new, what should we be interested in, when are the implementation deadlines and what is the best route towards compliance?

 With major new voice alarm standards set to come into operation in Britain in 2011 (British Standard EN 54-16:2008 and British Standard 5839 part 8: 2008), engineering managers worldwide are bound to be considering how their products will fare in the UK under new demands and how changes to products can be handled.

 There are two important things to consider about British Standard 5839 Part 8: 2008. Firstly, given the advances made throughout the industry over the past 10 years, it is sobering to think that this is a standard whose principal content dates from 1998. Secondly, voice alarm manufacturers should be aware that while it is often quoted as a requirement in system specification documents, British Standard 5839 Part 8: 2008 is in fact a code of practice for the design, installation, commissioning and maintenance of voice alarm systems. While the previous version did describe the requirements of products, the latest version lives up to its title and refers out to EN54-16:2008 for specific product function.

 Similarly, it is not possible to comply on a product level with the current standard governing sound systems for emergency purposes, British Standard EN 60849: 1998. The clue ought to be obvious from the title; this is a "system level" specification and any attempt to declare a product compliant to it is likely to be spurious, though this has not stopped several major players in the field alleging third-party accreditation when there is in fact no defined test regime.

While ten years is relatively recent in terms of certification when compared with other sectors, there is still much old-school thinking in the two voice alarm standards we are considering. They were written in an era when audio was mostly analogue, amplifiers were big, hot, unreliable beasts and software control systems were largely frowned upon. 


British Standard EN 54-16:2008 may level the playing field in the voice alarm sector 

PA VA system in use
The new standard will apply directly to any Voice Alarm equipment

The new standard that is causing interest throughout the British industry is BS EN 54-16:2008 which will apply directly to anything that a manufacturer refers to as Voice Alarm equipment or, more specifically, 'control and indicating equipment.' The distinction is that this is a product specification with a defined regime for testing and it will apply to everything from amplifiers to audio routers, in fact any component that is part of the core functionality of voice alarm.

British Standard EN 54-16:2008 is a standard that has been designed as a means of obtaining third-party accreditation. In the same way that all fire alarm systems have to be accredited by an approved testing house before they can be sold, VA systems are now going to be subjected to similar scrutiny. This is a sea change in the voice alarm sector and will have the welcome effect of levelling the playing field. However,  there are enough nursery and fairy tales cautioning us to be careful what we wish for to sound a note of warning. Even so, in contrast with British Standard 5839 part 8: 2008 which gives voice alarm manufacturers no specific guidance on what should be inside their units, British Standard EN 54-16:2008 really does relate to equipment and what products need to do.

The new British Standard 5838 Pt 8:2008 standard requires that voice alarm systems should be classified according to a graduated scale relating to the evacuation plan for a building. The categories are V1 to V5, V1 being the simplest such as the basic situation of a fire alarm panel connected to a voice alarm panel. In the event of the fire alarm going off, the VA simply gives an 'evacuate' announcement. The next two categories have different kinds of emergency microphones as well as elements of manual interaction and manual voice announcement. The highest category, V5, covers a complex alarm system at large installations such as a stadium, transport hub or shopping centre where there is a need for a sophisticated 3-D supervisory GUI such as ASL's iVENCS which can show what is happening at a location and help manage the location in the event of an emergency. To give an idea of scale, a standard London Underground station would be a V2 or V3 while a major national transportation hub like St Pancras International Station in London would be a V5.


Fire alarm guidelines based on voice alarm proximity in British Standard 5839 Part 8

For the first time in the UK, the standard has included recommendations for networked and radio-linked systems and there are configuration requirements for labelling elements. A significant statutory requirement is that connection to a fire alarm interface must be duplicated if the fire alarm is more than 10 metres away from the VA system. The various parties involved in design, installation, commissioning acceptance and verification can look at example certificates for each of those phases. This is a welcome development since certification allows each player to specify exactly what element of the design they have been responsible for.

But while there is clarity with these elements, elsewhere there is ambiguity, notably in the fact that BS 5839:2008 makes reference to British Standard EN 54-16:2008, which does not come into effect until 2011. The present situation is one of flux that should be clarified in a year's time.


Distinct functional conditions in British Standard EN 54-16

 A notable aspect of the new standard is that a VA system is required to operate in at least three distinct functional conditions. These are the quiescent condition where it is inactive or simply playing music, an active voice alarm condition where it is evacuating people either through automatic message or manual microphone and a fault warning condition.

 The main implication of these conditions for voice alarm manufacturers is how they are indicated and an immediate task may well be to modify the functioning of LEDs in order to be fully compliant. In the case of manual control – a panel with buttons to evacuate certain parts of a building – British Standard EN54-16 requires voice alarm and fault LED indication per zone. There is also a requirement to have only one emergency mic active at any one time while currently we can have different mics active across various zones.


Acknowledging commercial off-the-shelf software

Fire marshals evacuated by PA VA system
The new standard requires VA systems to operate in at least three distinct functional conditions

A significant aspect of British Standard EN54-16 is that the existence of commercial off-the-shelf (COTS) software is acknowledged for the first time. Previously, the convention was that voice alarm systems were designed from the ground up with every element being created in-house to the requirements of previous standards. By contrast, British Standard EN54-16 acknowledges the use of generic operating systems, distributed systems and Ethernet usage. The current conflicting standards will be withdrawn in April 2011 and compliance with British Standard EN54-16 in the EC will become a legal requirement under the European Committee for Standardisation and the Construction Products Directive.


Achieving compliance with British Standard EN54-16

Even a cursory glance at the standard will reveal that there is no scope for cutting corners. Manufacturers will need to co-operate with an accredited test house, ensure all testing is witnessed and will be unable to reuse test results even if they have demonstrably met the required criteria previously. This applies to both electromagnetic compatibility (EMC) testing and environmental testing.

The standard requires functional testing as well as EMC immunity assessment, and while these must be seen to be separate activities it is likely they will be performed together. ASL is currently analysing the requirements of the new standard and has created a separate validating team comprising EMC engineers, technical authors and software testers with the specific role of taking its public address and voice alarm product range through EN54-16 accreditation.
 

Dr Steve Harrison, ASL

 Dr Steve Harrison has worked in the professional audio industry for 20 years and has been jointly responsible for developing voice alarm products at ASL. His track record includes designing the first commercially-available 100V Class D amplifier for the VA market and the initial research he conducted after joining the company remains at the core of the adaptive Class D technology used throughout ASL’s product range. Steve is currently responsible for product design and the management of ASL's team of hardware and embedded software engineers.

Share with LinkedIn Share with Twitter Share with Facebook Share with Facebook
Download PDF version Download PDF version

In case you missed it

How Technology Helps London Fire Brigade With Incident Command
How Technology Helps London Fire Brigade With Incident Command

Drones give Incident Commanders an aerial view, increasing their situational awareness of fires and helping them to develop tactics to tackle them. Station Officer Lee Newman details how the technology was implemented by London Fire Brigade and the continued benefits. Identify external risks The Grenfell Tower fire has resulted in revisions to several operational procedures and the introduction of new equipment within the Brigade. A few months after the fire, the Brigade was tasked with setting up a trial to test the feasibility of having a drone capability to identify external risks and assess building stability at incidents, providing essential safety information that could facilitate ongoing internal firefighting operations. Implement the use of drones The Brigade implemented the use of drones and acquired a Matrice 210 V1 and a Phantom 4 Working with partners who had an existing drone capability, as well as drone experts, the Brigade began work to implement the use of drones and acquired a Matrice 210 V1 and a Phantom 4 as a trainer and reserve drone. In the summer of 2018, an Emergency Services bespoke course was run by Essex Police to train the Brigade’s team of drone pilots, who were all PfCO qualified within one week. From start to finish, it took just nine months to get London Fire Brigade’s drone team operational. Working of the drones On its first day of being available for incidents, the team received an order to attend a 15-pump fire at a leisure center, which was under renovation. They were asked to confirm if there were cylinders on the roof of the building and immediately put the drone to use. The team flew and relayed the camera footage onto a large screen that was fitted into a van provided for the trial. The drone footage was able to identify, to the Incident Commander’s satisfaction, that the cylinders were actually rolls of asphalt due to be laid on the roof as part of the renovation. If the drone concept could have proven its use in one job, this was it. The information from the drone allowed the Incident Commander to decide not to make it ‘cylinders confirmed’ and saved a lot of unnecessary extra appliance movements. Applications of drone Since that first callout, the team has been to around 300 incidents of six pumps or more, including persons in the water, fires, and various missing people’s incidents both in London and into other counties, assisting police forces. From start to finish, it took just nine months to get London Fire Brigade’s drone team operational Drone inventory The Brigade’s drone capability inventory includes a Matrice 300 with an H20T dual thermal and optical camera; a DJI Mavic 2 Enterprise Dual with multi attachments; a Mavic Air 2 and a Yuneec 520. The Brigade also has a Teradek live streaming device and multiple tablets for receiving the streamed footage. The Brigade operates with two Mitsubishi Outlander PHEVs – plug-in hybrid SUVs – and has split the drone equipment into two, with one vehicle carrying the drone and batteries, and the other carrying all the support kit and ancillaries. Working in dark conditions The drones are permitted to fly up to 400 ft above ground level or higher in an emergency and can fly as fast as 50 mph. They also can act as a loudspeaker to give instructions or reassurance and shine a bright spotlight in dark or low light conditions. 24/7 service The Brigade has eight pilots trained and operates a 24/7 service The Brigade has eight pilots trained and operates a 24/7 service. The team is working closely with its blue light partners, including the: Metropolitan Police Service, several search and rescue teams, and a host of fire services surrounding the capital, as well as giving advice to other upcoming drone teams around the UK. Use of drone in future The Brigade’s drone capability has been molded to how it sees the future and what it holds in the way of drone use. For example, the Brigade has developed a capability to drop water rescue aides to people at water incidents, which helps to keep them afloat long enough to be rescued. The drone can also be used alongside the swift water rescue teams to provide situational awareness of hazards and the resulting risks during the rescue phase. Delivering fire escape tools The Brigade also invested in fire escape hoods in late 2018 and has already demonstrated how one might be delivered via a drone to a balcony above the height of an aerial appliance while using the Mavic Enterprise 2 to relay instructions via the loudspeakers. These possible new uses are pushing the boundaries of the Brigade’s original concept and demonstrate how London Fire Brigade works to stay ahead of the curve. 

Chicago Bans Dogs From Firehouses, Despite Long-Held Tradition
Chicago Bans Dogs From Firehouses, Despite Long-Held Tradition

There is a long tradition of canines in the fire service, from Dalmatians riding shotgun in the fire truck to mixed breeds rescued from fires that later become the fire company mascot. The tradition has taken a hit recently in Chicago, where dogs are no longer allowed at firehouses after one station dog killed a smaller breed canine near a firehouse in the Englewood neighborhood. The incident The firehouse dog in Chicago, named Bones, was a mixed breed stray rescued off the street that was living at Engine 116 at 60th Street and Ashland Avenue. A neighbor was walking her smaller breed dog past the firehouse and watched in horror as Bones attacked and killed her small dog. After the incident, Chicago’s Acting Fire Commissioner Annette Nance-Holt issued a department memo: “Any and all prior permissions for dogs in the fire stations or on fire apparatuses are hereby revoked … effective immediately.” Chicago Firehouse dogs Most of Chicago’s firehouse dogs are strays that were picked up and brought to firefighters by the public. Fire crews and paramedics care for the dogs, train them, feed them and get them inoculated and spayed or neutered, then ask formal permission to keep the dogs on site. Historically, permission has been granted, in effect saving the dogs from being euthanized. Breed of choice The tradition of dogs and the fire service goes back centuries, to the 1700s, when carriage dogs first trotted alongside horse-drawn fire carriages. Dalmatians were the breed of choice, given their good temperament, calming effect on the horses Dalmatians were the breed of choice, given their good temperament, calming effect on the horses, and grace under pressure. The Fire Department of New York (FDNY) began utilizing Dalmatians as early as the 1870s. Dalmatians as firehouse ambassadors When motorized vehicles came on the scene, Dalmatians were already associated with firefighters, who continued to keep them on-site as firehouse residents and mascots. Increasingly, Dalmatians and other dogs became public ambassadors for firehouses and were involved in public education about fire safety and emergency preparedness for school and community groups. For example, Sparkles the Fire Safety Dog, a Dalmatian from Clarksville, Ark., was a character in her own set of children’s books about fire safety and traveled around the country teaching children about fire tips. reduce stress, provide comfort Currently, firehouse dogs are other breeds, too, many rescued from house fires or other tragedies. Firehouses often adopt dogs, who become symbols of resiliency, bravery, fortitude – and provide comfort and companionship for firefighters who face high levels of stress on the job. After the 9/11 attacks, two firefighters from Rochester, N.Y., gifted the FDNY Ladder 20 company a Dalmatian puppy, appropriately named Twenty. The dog served as a source of comfort to the firefighters, who lost seven members of the company in 9/11. Dogs recognize signals Taken in as a stray in 1929, a dog named Nip served 10 years with New York’s Engine Company No. 203. During his service, the dog was injured by broken glass, falling debris, scalding burns, and bruises from falling off the fire engine. Nip could recognize all bells and signals. On fire scenes, Nip could alert firefighters if he knew something was wrong and sometimes run into burning buildings to look for victims. Unfortunately, Nip was killed by a hit-and-run driver in front of the firehouse in 1939 (and was stuffed by a taxidermist and displayed at the firehouse until 1974). Dogs promote fire safety Dogs promote fire safety outside the firehouse Dogs also promote fire safety outside the firehouse. For example, accelerant-sniffing dogs are trained to detect minute traces of accelerants that may be used to start a fire, according to the State Farm Arson Dog Program. The special bond between firefighters and dogs is the stuff of legend, despite the recent unfortunate events in Chicago – an ignoble scar on a long, colorful history of dogs in the fire service. Hopes remain that the decision can somehow be reversed, based on social media postings. “This is the first tragedy I have heard of in … 25 years,” said the administrator of the Firehouse Pups group.

What Impact Has COVID-19 Had On The Fire Industry?
What Impact Has COVID-19 Had On The Fire Industry?

The COVID-19 pandemic has had ramifications for almost every industry, some more than others. With the pandemic stretching well into a second year, the non-medical consequences continue, and many are wondering about which of the required changes might become permanent. As regards the fire sector, we asked our Expert Panel Roundtable: What impact has COVID-19 had on the fire industry?

vfd