Features:

Due to the changes to the UL218 requirements for Limited Service Fire Pump Controllers, effective January 1, 2020, all Tornatech Model GPL and GPL+GLU controllers will be manufactured and supplied with the following features:

  • Circuit breaker (disconnection means)
    • Externally operable (flanged disconnect)
    • Continuous rating of 115% of FLC
    • Non-thermal type
    • Instantaneous trip not more than 20 times the FLC
  • Locked rotor protection
    • Between 8 and 20 seconds at locked rotor current
    • Three minutes at a minimum of 300% of FLC
  • Run test solenoid valve

The consequence of these changes requires a change in the size of the enclosure as follows:

Model

Size Prior to Jan. 1 2020

Size after Jan. 1 2020

GPL

20” w x 24” h x 8” d

20” w x 36” h x 12” d

GPL+GLU

40” w x 24” h x 8” d

36” w x 36” h x 12” d

The following limitations still apply:

  • Across the line starting only
  • Horsepower rating of maximum 30HP
  • Can only be installed where acceptable by the authority having jurisdiction Not accepted in FM insured property
  • The controllers will still be available in single phase configuration (220V to 240V – 1ph – 60Hz up to 15HP). However, seismic certification is no longer available.

Submittal Drawings:

Effective immediately, these new products can be included as part of your proposals. The website has been updated with the new submittal packages.

  • Related categories
  • Pumps

In case you missed it

WAGNER's Fire Protection Solutions At BUILDINX 2025
WAGNER's Fire Protection Solutions At BUILDINX 2025

WAGNER Group GmbH will be presenting pioneering solutions for fire protection in modern logistics properties at BUILDINX 2025 in Dortmund from November 18 to 20, 2025. The foc...

Spare A Minute For Maintenance
Spare A Minute For Maintenance

With new fire safety regulations around the corner and a renewed focus on responsible persons and coordination, Karen Trigg of Allegion UK discusses the significance of fire door h...

Fire-Dex Unveils Fire Investigation PPE For Safety
Fire-Dex Unveils Fire Investigation PPE For Safety

Fire investigators have long worked in a gray area of protection where full structural turnouts are overkill, but single-layer garments may not cover every single hazard they encou...

vfd