VIKING 23867AA VK1001 - Standard Response Upright Sprinkler (K5.6)

Technical Specification

Features:
  • Make: VIKING
  • Model code: 23867AA
  • Series: VK1001
  • Orientation: Upright
Additional info:

VK1001 - Standard Response Upright Sprinkler (K5.6)  Model (SIN): VK1001 Application: Standard Spray Response: Standard Response Temperature:  135 °F (57 °C) Element: 5mm Glass Bulb Orientation: Upright Style: Frame Style Thread Size:  1/2" NPT Finish: Standard Brass Occupancy Type: Light; Ordinary; Extra K-Factor: K5.6 (80) Approvals:  UL; cULus; FM Type: Wet

Read more
Make VIKING
Manufacturer VIKING Life - Saving Equipment A / S
Category Fire Protection>Fire Sprinklers
Model code 23867AA
Series VK1001
Orientation Upright

Product description

The VIKING VK1001 Standard Response Upright Sprinkler K5.6 (80.6) is a reliable fire safety component engineered for use in automatic fire sprinkler systems. This upright sprinkler is meticulously designed to uphold its standard response and coverage capabilities in various commercial and industrial environments.

Key technical specifications include a nominal K-factor of 5.6, and a minimum operating pressure of 7 psi (0.5 bar), ensuring optimal performance even in challenging conditions. The VK1001 is crafted from robust materials such as brass and stainless steel, making it suitable for usage in environments where corrosion resistance is crucial. With comprehensive listings and approvals from several recognized authorities, including cULus, FM, and VdS, this VK1001 model ensures compliance with international safety standards.

Distinctive Features

  • Nominal K-factor: 5.6 (80.6)
  • Temperature Rating: Minimum of -65°F (-55°C)
  • Maximum Pressure: Tested up to 500 psi (35 bar)
  • Material Composition: Brass, stainless steel, and PTFE
  • Approvals: cULus, FM, VdS, UKCA, and other global certifications

Ideal Use Cases

The VK1001 is specifically suited for installations demanding high reliability, such as light hazard, ordinary hazard, and extra hazard environments. It is further endorsed for use in regions following NFPA and FM installation standards, making it highly versatile for diverse occupancy types.