Viking - 23028JND-TQ - Residential Horizontal Sidewall Sprinkler (K5.8)

Technical Specification

Features:
  • Make: VIKING
  • Model code: 23028JND-TQ
  • Series: VK460
  • Orientation: Sidewall
  • NFPA temperature class: Ordinary
Additional info:

Max Pressure - 175 psi (12 bar) Response Type - Fast (Residential) Occupancy Type - Residential Thread Size - 1/2" NPT (15 mm BSP) Min Spacing - 8 ft (2,4 m) Max Spacing - 14 ft (4,3 m) x 26 ft (7,9 m) Orientation - Horizontal Sidewall Element Type - Glass Bulb

Read more
Make VIKING
Manufacturer VIKING Life - Saving Equipment A / S
Category Fire Protection>Fire Sprinklers
Model code 23028JND-TQ
Series VK460
Orientation Sidewall
NFPA temperature class Ordinary
Standards NFPA

Product description

The VIKING Freedom® Residential Horizontal Sidewall Sprinkler VK460, featuring a robust K5.8 factor, is engineered for high performance in residential fire protection systems. This meticulously designed, thermosensitive glass-bulb sprinkler is available in multiple finishes, including ENT coating, which makes it suitable for corrosive environments due to its corrosion-resistant properties. Its deflector and glass bulb allow it to meet rigorous residential sprinkler standards, expanding its application range effectively.

Key Features

  • Nominal K-factor of 5.8 (83.6 metric†) ensures efficient water use.
  • Operates with pressures up to a maximum of 175 psi, with factory testing at 500 psi.
  • Offered in finishes such as Brass, Chrome, and specialized coatings like White or Black Polyester, and Electroless Nickel PTFE (ENT).
  • Temperature ratings: 155 °F (68 °C) and 175 °F (79 °C) for adaptability in various environments.
  • Equipped with a 3 mm diameter glass bulb rated to -65 °F (-55 °C) for extreme conditions.

Ideal Use Cases

VIKING VK460 is particularly suited for residential environments requiring precise and reliable fire suppression. It's adaptable for both new installations and retrofits in homes, small apartments, and similar settings, ensuring optimal safety aligned with the NFPA standards. The corrosion-resistant finishes broaden its application to environments with potential exposure to corrosive elements.

The VK460 integrates seamlessly into hydraulically designed fire protection systems, offering optimal performance and compliance with stringent safety standards. Each unit is a testament to VIKING's commitment to excellence and reliability in residential fire safety solutions.

vfd