Globe Fire Sprinklers GL5685 horizontal sidewall sprinkler

Globe Fire Sprinklers GL5685 Fire Sprinkler
BrandGlobe Fire Sprinklers
Model Code GL5685
ESFR?No
StandardsNFPA
NFPA temperature classHigh
Model Info

Horizontal sidewall sprinkler. Listed for light hazard only with deflector from 4" to 12" below the ceiling. Nominal 'K' factor: 5.6 (80 metric). Thread Size: 1" NPT. Length: cULus variable to 48". Classification: high. Available sprinkler temperature: 57°C, 68°C, 79°C, 93°C, 141°C. Bulb colour: blue. NFPA maximum ceiling temperature: 107°C. FM Approved. Finishes: factory bronze, satin chrome, bright chrome ( available on special order).