RKI Instruments GP-01 single gas personal monitor for combustible gas

RKI Instruments GP-01 Detector
BrandRKI Instruments
Model Code GP-01
Model Info

Gas detected: combustible gas. Detection principle: catalytic combustion. Detection range: 0 - 100% LEL (1% LEL Increments). Alarm set points: 1st alarm 10% LEL; 2nd alarm 50% LEL; Over alarm 100% LEL. Preset alarms (user adjustable) : diffusion. Response time: T90 in 30 seconds. Accuracy: +/- 5% of full scale.

Power: alkaline dry cell Ni-Cad battery pack. Continuous operation: alkaline: 16 hours Ni-Cad: 8 hours. Dimension and weight: 1.4 x 4.1 x 0.8 inches; 3.5 ounces (100 g). Operating temp. and humidity: -20°C ~ 50°C; humidity below 90% RH (non-condensing).